Copyright© 2019  GREATWALL CABLE CO., LTD.
All rights reserved 
冀ICP备09018508号-1
Powerby: 300.cn

PRODUCTS

PVC insulated sheathed power cable

basic information
Release time:
2019-07-25
没有此类产品
PRODUCT DESCRIPTION

Use
This product is suitable for circuits of AC 50Hz and rated voltage 0.6/1kv for power transmission and distribution.

Working conditions
1)The maximum rated temperature of the cable conductor is 70 ℃.
2)The maximum temperature of the cable conductor does not exceed 160 ℃ in case of short circuit (the longest duration is no more than 5s).
3)The ambient temperature of the cable is not less than 0 ℃ during laying, and the minimum bending radius should be not less than10 times of the cable outer diameter.

Type and name

Type Name Scope of application
VV
VLV
PVC insulated PVC sheathed power cable Laid indoors, in the tunnels or pipelines, the cable cannot withstand exogenous pressure or mechanical force.
VV22
VLV22
PVC insulated steel-tape armored PVC sheathed power cable Laid indoors, in the tunnels or buried in the soil, the cable can withstand pressure and other exogenous actions.
VV32
VLV32
PVC insulated thin steel wire-armored PVC sheathed power cable Laid indoors, in the mines or water, the cable can withstand considerable tensions.
VV42
VLV42
PVC insulated thick steel wire-armored PVC sheathed power cable Laid in the shafts, water and other vertical occasions, the cable can withstand considerable axial tensions.
ZR-VV
ZR-VLV
PVC insulated PVC sheathed flame-retardant power cable Laid indoors, in the tunnels or pipelines, the cable cannot withstand exogenous pressure or mechanical force.
ZR-VV22
ZR-VLV22
PVC insulated steel-tape armored PVC sheathed flame-retardant power cable Laid indoors, in the tunnels or buried in the soil, the cable can withstand pressure and other exogenous actions.
ZR-VV32
ZR-VLV32
PVC insulated thin steel wire-armored PVC sheathed flame-retardant power cable Laid indoors, in the mines or water, the cable can withstand considerable tensions.
ZR-VV42
ZR-VLV42
PVC insulated thick steel wire-armored PVC sheathed flame-retardant power cable Laid in the shafts, water and other vertical occasions, the cable can withstand considerable axial tensions.


Structure size, Technical parameters

Nominal cross
section of the wire
mm2
The number of
single wires
in the conductor
Insulation
thickness
mm
Sheath
thickness
mm
Approximate
outer diameter

mm
Approximate weight
of the cable
DC resistance
of the wire
Test voltage
(kV/5min)
kg/km kg/km Ω/km Ω/km
Cu Al 20℃ Cu 20℃ Al
1×1.5 1 0.8 1.4 6.1 50.7 41.3 12.1 - 3.5
1×2.5 1 0.8 1.4 6.5 63.5 47.9 7.41 12.1 3.5
1×4 1 1.0 1.4 7.4 87.7 63.0 4.61 7.41 3.5
1×6 1 1.0 1.4 7.9 111.0 75.9 3.08 4.61 3.5
1×10 7 1.0 1.4 9.2 166.6 93.0 1.83 3.02 3.5
1×16 7 1.0 1.4 10.3 233.3 132.2 1.15 1.91 3.5
1×25 7 1.2 1.4 12.0 344.9 185.4 0.727 1.20 3.5
1×35 7 1.2 1.4 13.2 449.8 228.7 0.524 0.868 3.5
1×50 19 1.4 1.4 14.9 590.5 289.8 0.387 0.641 3.5
1×70 19 1.4 1.4 16.7 807.3 374.2 0.268 0.443 3.5
1×95 19 1.6 1.5 19.3 1102.0 501.4 0.193 0.320 3.5
1×120 37 1.6 1.5 20.9 1349.0 590.3 0.153 0.253 3.5
1×150 37 1.8 1.6 23.1 1654.0 721.3 0.124 0.206 3.5
1×185 37 2.0 1.7 25.6 2060.0 891.6 0.0991 0.164 3.5
1×240 61 2.2 1.8 28.8 2651.0 1114.0 0.0754 0.125 3.5
1×300 61 2.4 1.9 31.9 3323.0 1396.0 0.0601 0.100 3.5
1×400 61 2.6 2.0 35.5 4205.0 1742.0 0.0470 0.0778 3.5
1×500 61 2.8 2.1 39.7 5359.0 2128.0 0.0366 0.0605 3.5
1×630 91 2.9 2.2 43.7 6707.0 2605.0 0.0283 0.0469 3.5
1×800 61 2.9 2.4 46.1 8064.0 3104.0 0.0221 0.0367 3.5

 

On a
XLPE insulated power cable
The next article
PVC insulated sheathed control cable