PRODUCTS

Carbon fiber aerial cable

basic information
Release time:
2019-07-23
没有此类产品
PRODUCT DESCRIPTION

Use
This product is suitable for overhead power lines of AC rated voltage U (Um) 10 (12) KV.

Working conditions
1) The maximum long-term allowable working temperature of the cable conductor is 90 ℃
2) The laying temperature should be not lower than -20 ℃
3) The maximum temperature of the conductor should not exceed 250℃ in case of short circuit (the longest duration is no more than 5s)  
 
Type and name (Table 1)
 
Type Section
(Aluminum/steel)
mm2
Name Main uses
JKLGYJ-10 10/2-500/65

10kV steel-core aluminum XLPE insulated aerial cable

Suitable for fixed laying of 10kV overhead power lines
When the cable is laid and erected, a certain distance between the cable and trees should be kept,
When the cable operates, frequent contact between the cable and trees is allowed.


Structure size, Technical parameters (Table 2-14)

Nominal cross section
Aluminum/steel
(mm2)
Structure, Pieces/Diameter
(mm)
Compacted conductor’s
outer diameter
reference
(mm)
Inner shield
thickness
(mm)
Insulation
thickness
(mm)
Cable outer
diameter reference
(mm)
Conductor’s
maximum

(Ω/km)
Calculate breaking
force (not less than)
N
Cable reference
weight
(kg/km)
10/2 6/1.50 1/1.50 4.28 1.0 3.4 13.1 0.7060 4120 159
16/3 6/1.85 1/1.85 5.27 1.0 3.4 14.1 1.7790 6130 194
25/4 6/2.32 1/2.32 6.60 1.0 3.4 15.4 1.1310 9290 270
35/6 6/2.72 1/2.72 7.75 1.0 3.4 16.6 0.8230 12630 304
50/8 6/3.20 1/3.20 9.12 1.0 3.4 17.9 0.5496 16870 375
50/30 12/2.32 7/2.32 11.02 1.0 3.4 19.8 0.5692 42620 577
70/10 6/3.80 1/3.80 10.83 1.0 3.4 19.6 0.4217 23390 477
70/40 12/2.72 7/2.72 12.92 1.0 3.4 21.7 0.4141 58300 741
95/15 26/2.15 7/2.15 12.93 1.0 3.4 21.7 0.3058 35000 611

 